Programmable logic controllers

Before the advent of solid-state logic circuits, logical control systems were designed and built exclusively around electromechanical relays. Relays are far from obsolete in modern design, but have been replaced in many of their former roles as logic-level control devices, relegated most often to those applications demanding high current and/or high voltage switching.

Systems and processes requiring "on/off" control abound in modern commerce and industry, but such control systems are rarely built from either electromechanical relays or discrete logic gates. Instead, digital computers fill the need, which may be programmed to do a variety of logical functions.

In the late 1960's an American company named Bedford Associates released a computing device they called the MODICON. As an acronym, it meant Modular Digital Controller, and later became the name of a company division devoted to the design, manufacture, and sale of these special-purpose control computers. Other engineering firms developed their own versions of this device, and it eventually came to be known in non-proprietary terms as a PLC, or Programmable Logic Controller. The purpose of a PLC was to directly replace electromechanical relays as logic elements, substituting instead a solid-state digital computer with a stored program, able to emulate the interconnection of many relays to perform certain logical tasks.

A PLC has many "input" terminals, through which it interprets "high" and "low" logical states from sensors and switches. It also has many output terminals, through which it outputs "high" and "low" signals to power lights, solenoids, contactors, small motors, and other devices lending themselves to on/off control. In an effort to make PLCs easy to program, their programming language was designed to resemble ladder logic diagrams. Thus, an industrial electrician or electrical engineer accustomed to reading ladder logic schematics would feel comfortable programming a PLC to perform the same control functions.

PLCs are industrial computers, and as such their input and output signals are typically 120 volts AC, just like the electromechanical control relays they were designed to replace. Although some PLCs have the ability to input and output low-level DC voltage signals of the magnitude used in logic gate circuits, this is the exception and not the rule.

Signal connection and programming standards vary somewhat between different models of PLC, but they are similar enough to allow a "generic" introduction to PLC programming here. The following illustration shows a simple PLC, as it might appear from a front view. Two screw terminals provide connection to 120 volts AC for powering the PLC's internal circuitry, labeled L1 and L2. Six screw terminals on the left-hand side provide connection to input devices, each terminal representing a different input "channel" with its own "X" label. The lower-left screw terminal is a "Common" connection, which is generally connected to L2 (neutral) of the 120 VAC power source.

Inside the PLC housing, connected between each input terminal and the Common terminal, is an opto-isolator device (Light-Emitting Diode) that provides an electrically isolated "high" logic signal to the computer's circuitry (a photo-transistor interprets the LED's light) when there is 120 VAC power applied between the respective input terminal and the Common terminal. An indicating LED on the front panel of the PLC gives visual indication of an "energized" input:

Output signals are generated by the PLC's computer circuitry activating a switching device (transistor, TRIAC, or even an electromechanical relay), connecting the "Source" terminal to any of the "Y-" labeled output terminals. The "Source" terminal, correspondingly, is usually connected to the L1 side of the 120 VAC power source. As with each input, an indicating LED on the front panel of the PLC gives visual indication of an "energized" output:

In this way, the PLC is able to interface with real-world devices such as switches and solenoids.

The actual logic of the control system is established inside the PLC by means of a computer program. This program dictates which output gets energized under which input conditions. Although the program itself appears to be a ladder logic diagram, with switch and relay symbols, there are no actual switch contacts or relay coils operating inside the PLC to create the logical relationships between input and output. These are imaginary contacts and coils, if you will. The program is entered and viewed via a personal computer connected to the PLC's programming port.

Consider the following circuit and PLC program:

When the pushbutton switch is unactuated (unpressed), no power is sent to the X1 input of the PLC. Following the program, which shows a normally-open X1 contact in series with a Y1 coil, no "power" will be sent to the Y1 coil. Thus, the PLC's Y1 output remains de-energized, and the indicator lamp connected to it remains dark.

If the pushbutton switch is pressed, however, power will be sent to the PLC's X1 input. Any and all X1 contacts appearing in the program will assume the actuated (non-normal) state, as though they were relay contacts actuated by the energizing of a relay coil named "X1". In this case, energizing the X1 input will cause the normally-open X1 contact will "close," sending "power" to the Y1 coil. When the Y1 coil of the program "energizes," the real Y1 output will become energized, lighting up the lamp connected to it:

It must be understood that the X1 contact, Y1 coil, connecting wires, and "power" appearing in the personal computer's display are all virtual. They do not exist as real electrical components. They exist as commands in a computer program -- a piece of software only -- that just happens to resemble a real relay schematic diagram.

Equally important to understand is that the personal computer used to display and edit the PLC's program is not necessary for the PLC's continued operation. Once a program has been loaded to the PLC from the personal computer, the personal computer may be unplugged from the PLC, and the PLC will continue to follow the programmed commands. I include the personal computer display in these illustrations for your sake only, in aiding to understand the relationship between real-life conditions (switch closure and lamp status) and the program's status ("power" through virtual contacts and virtual coils).

The true power and versatility of a PLC is revealed when we want to alter the behavior of a control system. Since the PLC is a programmable device, we can alter its behavior by changing the commands we give it, without having to reconfigure the electrical components connected to it. For example, suppose we wanted to make this switch-and-lamp circuit function in an inverted fashion: push the button to make the lamp turn off, and release it to make it turn on. The "hardware" solution would require that a normally-closed pushbutton switch be substituted for the normally-open switch currently in place. The "software" solution is much easier: just alter the program so that contact X1 is normally-closed rather than normally-open.

In the following illustration, we have the altered system shown in the state where the pushbutton is unactuated (not being pressed):

In this next illustration, the switch is shown actuated (pressed):

One of the advantages of implementing logical control in software rather than in hardware is that input signals can be re-used as many times in the program as is necessary. For example, take the following circuit and program, designed to energize the lamp if at least two of the three pushbutton switches are simultaneously actuated:

To build an equivalent circuit using electromechanical relays, three relays with two normally-open contacts each would have to be used, to provide two contacts per input switch. Using a PLC, however, we can program as many contacts as we wish for each "X" input without adding additional hardware, since each input and each output is nothing more than a single bit in the PLC's digital memory (either 0 or 1), and can be recalled as many times as necessary.

Furthermore, since each output in the PLC is nothing more than a bit in its memory as well, we can assign contacts in a PLC program "actuated" by an output (Y) status. Take for instance this next system, a motor start-stop control circuit:

The pushbutton switch connected to input X1 serves as the "Start" switch, while the switch connected to input X2 serves as the "Stop." Another contact in the program, named Y1, uses the output coil status as a seal-in contact, directly, so that the motor contactor will continue to be energized after the "Start" pushbutton switch is released. You can see the normally-closed contact X2 appear in a colored block, showing that it is in a closed ("electrically conducting") state.

If we were to press the "Start" button, input X1 would energize, thus "closing" the X1 contact in the program, sending "power" to the Y1 "coil," energizing the Y1 output and applying 120 volt AC power to the real motor contactor coil. The parallel Y1 contact will also "close," thus latching the "circuit" in an energized state:

Now, if we release the "Start" pushbutton, the normally-open X1 "contact" will return to its "open" state, but the motor will continue to run because the Y1 seal-in "contact" continues to provide "continuity" to "power" coil Y1, thus keeping the Y1 output energized:

To stop the motor, we must momentarily press the "Stop" pushbutton, which will energize the X2 input and "open" the normally-closed "contact," breaking continuity to the Y1 "coil:"

When the "Stop" pushbutton is released, input X2 will de-energize, returning "contact" X2 to its normal, "closed" state. The motor, however, will not start again until the "Start" pushbutton is actuated, because the "seal-in" of Y1 has been lost:

An important point to make here is that fail-safe design is just as important in PLC-controlled systems as it is in electromechanical relay-controlled systems. One should always consider the effects of failed (open) wiring on the device or devices being controlled. In this motor control circuit example, we have a problem: if the input wiring for X2 (the "Stop" switch) were to fail open, there would be no way to stop the motor!

The solution to this problem is a reversal of logic between the X2 "contact" inside the PLC program and the actual "Stop" pushbutton switch:

When the normally-closed "Stop" pushbutton switch is unactuated (not pressed), the PLC's X2 input will be energized, thus "closing" the X2 "contact" inside the program. This allows the motor to be started when input X1 is energized, and allows it to continue to run when the "Start" pushbutton is no longer pressed. When the "Stop" pushbutton is actuated, input X2 will de-energize, thus "opening" the X2 "contact" inside the PLC program and shutting off the motor. So, we see there is no operational difference between this new design and the previous design.

However, if the input wiring on input X2 were to fail open, X2 input would de-energize in the same manner as when the "Stop" pushbutton is pressed. The result, then, for a wiring failure on the X2 input is that the motor will immediately shut off. This is a safer design than the one previously shown, where a "Stop" switch wiring failure would have resulted in an inability to turn off the motor.

In addition to input (X) and output (Y) program elements, PLCs provide "internal" coils and contacts with no intrinsic connection to the outside world. These are used much the same as "control relays" (CR1, CR2, etc.) are used in standard relay circuits: to provide logic signal inversion when necessary.

To demonstrate how one of these "internal" relays might be used, consider the following example circuit and program, designed to emulate the function of a three-input NAND gate. Since PLC program elements are typically designed by single letters, I will call the internal control relay "C1" rather than "CR1" as would be customary in a relay control circuit:

In this circuit, the lamp will remain lit so long as any of the pushbuttons remain unactuated (unpressed). To make the lamp turn off, we will have to actuate (press) all three switches, like this:

This section on programmable logic controllers illustrates just a small sample of their capabilities. As computers, PLCs can perform timing functions (for the equivalent of time-delay relays), drum sequencing, and other advanced functions with far greater accuracy and reliability than what is possible using electromechanical logic devices. Most PLCs have the capacity for far more than six inputs and six outputs. The following photograph shows several input and output modules of a single Allen-Bradley PLC.

With each module having sixteen "points" of either input or output, this PLC has the ability to monitor and control dozens of devices. Fit into a control cabinet, a PLC takes up little room, especially considering the equivalent space that would be needed by electromechanical relays to perform the same functions:

One advantage of PLCs that simply cannot be duplicated by electromechanical relays is remote monitoring and control via digital computer networks. Because a PLC is nothing more than a special-purpose digital computer, it has the ability to communicate with other computers rather easily. The following photograph shows a personal computer displaying a graphic image of a real liquid-level process (a pumping, or "lift," station for a municipal wastewater treatment system) controlled by a PLC. The actual pumping station is located miles away from the personal computer display:

Motion Controllers

Programmable Logic Controllers ( PLCS ) & Programmable Logic Controller


Some programmable logic controllers ( PLCS ) are equipped to solve problems involving mathematical functions such as sine, cosine, tangent, xy, y root of x, e sub x , natural logarithms, and common logarithms. Such calculations are often required for energy management, process control, process modeling, real-time error correction, and many other applications.

And while ladder logic is still the standard industry programming language for programmable logic controllers ( PLCS ), the trend is toward state logic, sequential function charts, graphics, and versions that are programmable in Basic, C, or other high-level languages.

The ability to handle analog signals along with arithmetic and other complex calculations has made programmable logic controllers ( PLCS ) suitable for the control of processes as well as for the control of machines. Typical applications for programmable logic controllers ( PLCS ) are mineral and chemical processing, water and waste treatment, and petroleum collection and distribution. In many of these applications a programmable logic controller ( PLCS ) can complement conventional analog control systems by handling sequence problems as well as a portion of the analog calculation and control. In support of those functions, some programmable logic controllers ( PLCS ) now have the ability to store recipes for batch processing, reducing the need for manual inputs.

In further support of their process-control capabilities, some programmable logic controllers ( PLCS ) can be equipped to solve complex equations such as proportional-integral-derivative equations required for the control of many processes. A sophisticated programmable logic controller ( PLCS ) is capable of performing these calculations on many different portions of a process simultaneously.

Programmable Logic Controller

First, the PLC will require a proper enclosure and output loads, such as room lights, should have their own relay panel. The relay panel is installed above or below the PLC enclosure depending on the output wiring of the PLC. Mount the PLC horizontally to provide proper ventilation. You cannot mount the PLC vertically, upside down, or on a flat horizontal surface. Provide a minimum clearance of 40mm between the PLC and all sides of the enclosure.

Remember to allow for other items, like a Lutron interface unit, to be mounted in the same PLC enclosure. There should also be at least 80mm of clearance between the PLC and wiring that runs parallel to the unit.

PLCs can be secured to an enclosure by using mounting rails. They are approximately 35mm high, with a depth of 7mm. If you mount the PLC on a rail, do consider using end brackets on each side of the PLC. The end bracket helps keep the PLC from sliding horizontally along the rail, reducing the possibility of accidentally pulling the wiring loose.

The ground terminal on the PLC must be connected to a good common ground reference (Earth ground). One method of providing an adequate common ground reference is connection to the incoming power system ground. Most PLCs have no internal fuses for the input power circuits, so external circuit protection is needed to ensure the safety of personnel and safe operation of the equipment itself. When operating the PLC from 110/125 VAC, it is only necessary to fuse the line (L) lead; it is not necessary to fuse the neutral (N) lead.

Most connections, indicators, and terminals on a PLC are located on its front panel. The communication ports are located on front of the PLC as are the option card slots and the mode selector switch.

The PLC terminals are divided into two groups. Each group has its own terminal block. The outputs and power wiring are on one block, and the input wiring is on the other. In some instances, it may be desirable to remove the terminal block for easy wiring. The terminal block is designed for easy removal with just a small screwdriver. Minimum wire sizes, color coding, and general safety practices should comply with appropriate electrical codes and standards for your area. Each terminal connection of the PLC can accept one 16 AWG wire or two 18 AWG size wire. Avoid running DC wiring close to AC wiring where possible.

The PLC systems are designed to be powered by 110/125 VAC. Electrical power in some areas where the PLCs are installed is not always stable and storms can cause power surges. Due to this, powerline filters are recommended for protecting the PLCs from power surges.

Evaluate any installations where the ambient temperature may approach the lower or upper limits of the PLC specifications. If you suspect the ambient temperature will not be within the operating specification for the PLC system, measures such as installing a cooling/heating source must be taken to get the ambient temperature within the range of specifications.

TS-PLC (Embedded Programmable Logic Controller)

The TS-PLC is a microcontroller based solution for remote sensing and control in commercial and industrial applications. It incorporates a built-in custom BIOS to allow field reprogramming and upgrading. The default TS-PLC software executes a programmable logic controller model documented in the software section.

Hardware Description

The TS-PLC operates in conjunction with the TS-PLC-MASTER unit. A MASTER unit is required in order to program the TS-PLC device(s). The MASTER provides a web based interface for editing ladder logic and committing programs to TS-PLC devices. In some configurations the MASTER cannot be disconnected from the TS-PLC devices after they are programmed, but must instead remain connected to the serial network during operation of the those devices:

  • When the interface used is RS-485, and more then one TS-PLC is connected, and the TS-PLC units must communicate with each other for any reason. In this case, the TS-PLC-MASTER is required to remain connected to all units to perform the role of RS-485 master.
  • If the TS-PLC-MASTER has the RTC option, and any of the TS-PLC devices needs to use the current date or time as part of its operation. In this case, the devices that need this information must remain in communication with the MASTER in order to receive period time notifications.

The TS-PLC units and TS-PLC-MASTER can be networked (connected) across one of the following serial communications interfaces, at 115.2kbps:

  • RS-485
  • wireless radio (optional)
  • RS-232 (coming soon)
  • USB (coming soon)

The TS-PLC has a ten position industrial grade removable screw-down terminal strip for I/O connections:

PositionInput
function

name
Output
name

function
1GNDground

2ADC210-bit Analog to Digital ConvertorX+RS-485 mode only
3ADC310-bit Analog to Digital ConvertorX-RS-485 mode only
4ADC410-bit Analog to Digital ConvertorOUT4low-side switch
5ADC510-bit Analog to Digital ConvertorOUT5low-side switch
6ADC610-bit Analog to Digital ConvertorOUT6low-side switch
7ADC710-bit Analog to Digital ConvertorOUT7 high or low side switch
8ADC810-bit Analog to Digital ConvertorOUT8 high or low side switch
9VCCpower (4.7-30V DC)

10GNDground


Notes:

  • The high side switches when on will output to within about a diode drop of whatever input voltage you use, and are (cumulatively) current limited by a 400mA polyfuse.
  • The low side switches all have built-in clamp diodes so can be used to drive relays; maximum current is 200mA.
  • The TS-PLC can either be powered from the VCC input, or from USB

There are three addition I/Os which do not have connectors:

NameFunction
GLEDGreen LED
RLEDRed LED
TEMP10-bit Temperature Sensor (optional)


Programmable Logic Controller language

Overview

PLC controllers have been developed as a low cost flexible alternative to old relay logic controllers used in process and automated manufacturing control. They have numerous advantages over the relay logic systems including the lower cost, size, greater reliability and more functions than older systems. The technology that has allowed their development is the microprocessor/microchip technology. This allows for easy reprogramming of the control programs stored within the PLC memory and eliminates the need for any hardware modifications when a different control process is to be implemented. In the interest of simplicity and greater efficiency of programming a common set of programming standards and languages has been adopted across all PLC platforms.

This report focuses on the IEC 1131-3 standard and the set of four graphical and textual languages currently in use in the PLC programming.

The basic PLC system configuration and internal operation is provided, however the main focus is on the actual programming languages which are evaluated in detail. For each language the main application area is defined with the main strengths stressed, followed by a detailed account of the various instructions that are the building blocks of the programming language.

Network and Web-Managed Programmable Logic Controller (PLC) with PSU

The Networked Programmable Logic Controller (PLC-1608) has 16 Inputs and 8 Outputs


This unique PLC (Programmable Logic Controller) allows up to 16 inputs to be evaluated and up to 8 relay isolated outputs to be controlled.


Unique features include that the device can be connected directly to an Ethernet LAN. A built in web-site allows for configuration and status display of the controller thus no front panel required.

An optional A/D and D/A board allowing for 8 Analog Input and 8 Analog Output channels to be evaluated or be controlled.

Easy to understand programming language.

The controller is ideal to replace older TTL type controllers that for example controlled half automatic screen printing equipment, security access curtains, punch presses, sheers and press breaks.

But also ideal for remote control of motors, fans for factory or environmental monitoring applications.

The controller has a power supply and battery charger included which can run the controller fully functioning for up to 8 days.

A built in timer and clock which can syncronize with a timeserver, or be connected to Ringdale's Satellite Time Server keeps accurate time and can spawn actions at pre-set times.

The Ringdale PLC-1608 is ideal for solving small automation and robotics problems.

The PLC can also easily integrate into larger industrial applications and communication between devices through the network give the device unparalleled ability and flexibility.

Comes with power supply and battery charger in a rugged enclosure.

Allen Bradley MicroLogix 1500 PLC in Lookout

This document covers an example for configuring Allen Bradley MicroLogix 1500 PLC for Lookout, or Lookout Protocol Drivers using direct serial connection. This PLC uses a special cable by Allen Bradley to connect to a PC. The cable model number we are using is 1761-CBL-PM02.
1. Start Lookout and create a new object: by selecting Object >> Create.

2. Select AB_Logix from the list.


3. Configure the object properties using the exact communication settings from the proprietary software (the image below correspond to a specific PLC configuration, your settings may be different). Click OK when you are done.


4. At this point, the PLC should be configured in Lookout and you can access its object data members.

For an example of how to access Lookout object data members, refer to the tutorial in Accessing Lookout Object Datamembers.

If you need help in accessing the PLC from the LabVIEW DSC module, refer to the document Connecting LabVIEW OPC Client through DataSocket connection.

For more information about AB_Logix object data members, please consult the Lookout Help.

Refer to Notes on Allen Bradley PLC Addressing for more information about using the AB_Logix object.